The inControl offers on/off and variable-speed controls. Common applications involve using contactors to set schedules for lighting. Variable speed controls can be used for controlling valves and fans. The inControl has options to communicate with the inGate via wired or wireless (Zigbee). The inControl control module has the following inputs and outputs for receiving and passing commands from user interaction, automated schedules, or analytics:

  • Analog input x 2: 0-5V DC
  • Analog output x 2: 4-20 mA
  • Digital input x 4: 0-24 VAC & 5-30 VDC
  • Digital output x 8: 0-60 VDC & 0-42 VAC
  • 2A continuous & 6A < 10Ms
  • Communication: RS485 and Zigbee

Power:

  • 10-30 VDC
  • 24 VDC Minimum for Analog Output

Operating Environment:

  • Temperature: -40°C to 60°C (-40 to 140°F) Humidity: 0-95% Non-Condensing

Dimensions:

  • Length 4.125” Width 4.375” Height 2.5”

Future integration could include a light or motion sensor to impact lighting controls.